Input/Output Circuit Specifications

Product Description

Current Availability

The following figures illustrate the maximum current possible for each panel output circuit and the

total output current available from the power supply. Refer to Section 6, “Power Supply Calcula-

tions” for additional current draw by option cards that must be considered when determining total

standby and alarm currents.

TB20

TB21

TB19

TB24

TB23

TB17

Primary 50W
Speaker Circuit

3.3 amps max.

Secondary 50W
Speaker Circuit-
Optional Amplifier
Installed

3.3 amps max.

NAC Circuit

2.0 amps max.

Aux. Power

0.5 amp max.

Speaker Volume
Control Override

0.25 amp max.

External Operator
Interface Power

0.8 amp max.

Standby

2.0 amps max.

(includes background

music) with external

charger. Refer to

Section 6.

Alarm

7.5 amps

max.

Figure 1.2 Current Availability - 100 Watt System