3. Measurement Mode

18

3.3 How to Measure Flow Rate in the Duct [Flow Rate Mode]

Display Key

Procedure

MENU

(1) Press MENU key.

, ▽

SET

(2) Select 2. MEASUREMENT.

Then press SET key.

, ▽

SET

(3) Select 3. FLOW RATE.

Then press SET key.

, ▽

SET

SET

(4) Set the measurement condition

in the same manner as when

configuring Average Mode (P14).

When the measurement condition is configured, select 7.

SET OK!, and press SET key.

Air Volume (F) = Average Air Velocity (U) × Cross Section (AREA)

indicated in m³/hour and m³/min

Example

POINT 1 --- AVE 1 = Σ DATA (N)/N
POINT 2 --- AVE 2 =Σ DATA (N)/N

POINT M --- AVE M =Σ DATA (N)/N

* To start a measurement at each point: START/STOP key
* For detailed information on measuring at each point, refer to 3.2 How to

Collect Data at Certain Time Intervals [Interval Mode] (P16).

Average Air Velocity

U =

(AVE1+AVE2+···AVE N)

No. of Points (M)

Measuring Point

(POINT)

Duct Area

r1=0.316R
r2=0.548R
r3=0.707R
r4=0.837R
r5=0.949R

R

r1 r2 r3

r4

r5

Measuring Point

Š Calculation result

Š Measurement

FLOW RATE

(a)

To select the item to be
changed

, ▽⇨SET

To change setting value

and YES/NO.

, ▽⇨SET

Setting is complete.
7. SET OK! ⇨ SET

< MENU >

1. MONITOR

2

. MEASUREMENT

3. DATA OUTPUT
4. MEMORY CLEAR
5. UTILITY

< MEASUREMENT >

1. AVERAGE

2. INTERVAL

3

. FLOW RATE

< FLOW >

1. S-TIME(S) 01
2. DATA (N) 010
3. POINTS 016
4. AREA(m2) 0.100
5. MEMORY YES
6. PRINT YES

7

. SET OK!

<Measurement Setting

Screen>