3.4 Error list / Maintenance manager

With one or several errors, the extended operating level
always starts with the error list. Signalling an actual entry
in the error list (alarm, error) is done by the Err LED in
the display. To reach the error list press Ù twice.

Error list:

Name

Description

Reason

Possible remedial action

E.1

Internal error,

cannot be removed

- E.g. defective EEPROM

- Contact West service
- Return unit to our factory

E.2

Internal error, can

be reset

- e.g. EMC trouble

- Keep measurement and power supply

cables in separate runs

- Ensure that interference suppression of

contactors is provided

E.3

Configuration error,

can be reset

- wrong configuration
- missing configuration

- Check interaction of configuration /

parameters

E.4

Hardware error

- Codenumber and hardware are

not identical

- Contact West service
- Elektronic-/Optioncard must be exchanged

FbF.1

Sensor break INP1 - Sensor defective

- Faulty cabling

- Replace INP1 sensor
- Check INP1 connection

Sht.1

Short circuit INP1 - Sensor defective

- Faulty cabling

- Replace INP1 sensor
- Check INP1 connection

POL.1

INP1polarity error - Faulty cabling

- Reverse INP1 polarity

FbF.2

Sensor break INP2 - Sensor defective

- Faulty cabling

- Replace INP2 sensor
- Check INP2 connection

Sht.2

Short circuit INP2 - Sensor defective

- Faulty cabling

- Replace sensor INP2
- Check INP2 connection

POL.2

INP2 polarity

- Faulty cabling

- Reverse INP2 polarity

FbF.3

Sensor break INP3 - Sensor defective

- Faulty cabling

- Replace INP3 sensor
- Check INP3 connection

Sht.3

Short circuit INP3 - Sensor defective

- Faulty cabling

- Replace sensor INP3
- Check INP3 connection

POL.3

INP3 polarity

- Faulty cabling
-

- Reverse INP3 polarity

HCA

Heating current

alarm (HCA)

- Heating current circuit

interrupted, I<

HC.A or I>

HC.A (dependent of
configuration)

- Heater band defective

- Check heating current circuit
- If necessary, replace heater band

Operation

KS 90-1

p / KS 92-1

p

13

Error list / Maintenance manager

1200

1199

°C

°F

SP.2

SP.E

para

func

Ada

Err

Err LED status

Signification

Proceed as follows

blinks(status 2)

Alarm due to

existing error

Determine the error type in the error list After

error correction the unit changes to status 1

lit(status 1)

Error removed, alarm not ack-

nowledged

Acknowledge the alarm in the error list pressing

key ÈorÌ The alarm entry was deleted (status 0).

off(status 0)

No error, all alarm entries deleted -Not visible except when acknowledging