4.2 Set-point processing

The set-point processing structure is shown in the following picture:

Set-point gradient / ramp
To prevent setpoint step changes, a maximum rate of change is adjustable for pa-
rameter r setpoint r

r.SP. This gradient acts both in positive and negative di-

rection.

With parameter

r.SP set to OFFas in the factory setting, the gradient is switched

off and setpoint changes are made directly.

Configuration level

Set-point processing

42

KS 90-1

p / KS 92-1

p

0

1

Ü

Xeff

SP.2

SP.E

Internal set-point

Programmer

*

Ö

SP.Hi

SP.Lo

r.SP

- LED

external
set-point

Limiting

Ramp

2nd
set-point

Effektive
set-point

Ü

+

+

8

9

1200

1199

°C

°F

SP.2

SP.E

para

func

Ada

Err

The ramp starts at process value with the following switchings:
- int / ext-setpoint switching
-

/

switching

- Manual-/ Automatic switching
- at power on

SP SP.2

Index:

Ь
*
Ц

: int/ext-setpoint switching
: configuration
:

/

switching

SP.Fn

SP SP.2

Advertising