Technical data 74, Current signal measuring range 74, Resistance thermometer measuring range 74 – West Control Solutions KS 92-1 Programmer manual User Manual

Page 74: Thermocouple measuring range 74, Voltage signal measuring range 74, 11 technical data, Technical data

Advertising
background image

11

Technical data

INPUTS

PROCESS VALUE INPUT INP1

Resolution:

> 14 bits

Decimal point:

0 to 3 digits behind the
decimal point

Dig. input filter:

adjustable 0,000...9999 s

Scanning cycle:

100 ms

Measured value
correction:

2-point or offset correction

Thermocouples

r

Table 1 (page 77 )

Internal and external temperature compensa-
tion

Input resistance:

³ 1 MW

Effect of source resistance:

1

mV/W

Internal temperature compensation

Maximal additional error:

± 0,5 K

Sensor break monitoring

Sensor current:

£ 1 mA

Configurable output action

Thermocouple to specification

Measuring range -25...75mV in conjunction
with the linearization can be used for connect-
ing thermocouples which are not included in
Table 1.

Resistance thermometer

r

Table 2 (page 77 )

Connection:

3-wire

Lead resistance:

max. 30 Ohm

Input circuit monitor:

break and short circuit

Special measuring range
BlueControl (engineering tool) can be used to
match the input to sensor KTY 11-6 (character-
istic is stored in the controller).

Physical measuring range:

0...4500 Ohm

Linearization segments

16

Current and voltage signals

r

Table 3 (page 77 )

Span start, end of span: anywhere within measuring

range

Scaling:

selectable -1999...9999

Linearization:

16 segments, adaptable
with BlueControl

Decimal point:

adjustable

Input circuit monitor:

12,5% below span start
(2mA, 1V)

SUPPLEMENTARY INPUT INP2

Resolution:

> 14 bits

Scanning cycle:

100 ms

Heating current measurement

via current transformer (

® Accessory equip-

ment)

Measuring range: 0...50mA AC
Scaling:

adjustable -1999...0,000...9999 A

Current measuring range

Technical data as for INP1

Potentiometer

r Table 2 (page 77 )

SUPPLEMENTARY INPUT INP3 (OPTION)

Resolution:

> 14 bits

Scanning cycle:

100 ms

Technical data as for INP1 except 10V range.

CONTROL INPUTS DI1, DI2

Configurable as switch or push-button!
Connection of a potential-free contact suitable
for switching “dry” circuits.

Switched voltage:

5 V

Current:

100

mA

CONTROL INPUTS DI2, DI3 (OPTION)

The functions of control input di2 on the analog
card and of di2 on the options card are logically
ORed. Configurable as direct or inverse
switches or keys.
Optocoupler input for active triggering.

Technical data

74

KS 90-1

p / KS 92-1

p