4.4 Configuration examples

4.4.1 On-Off controller / Signaller (inverse)

ConF/Cntr: SP.Fn = 0

set-point controller

C.Fnc = 0

signaller with one output

C.Act = 0

inverse action (e.g. Heating
applications)

ConF/Out.1: O.Act = 0

action

Out.1 direct

Y.1

=

1

control output Y1 active

PArA/Cntr: Hysl = 0...9999

switching difference (below
set-point)

PArA/Cntr: HysH = 0...9999

switching difference (above
set-point)

PArA/SEtP: SP.LO = -1999...9999 set-point limit low for Weff

SP.Hi = -1999...9999 set-point limit high for Weff

g

For direct signaller action, the controller action must be changed
(

ConF / Cntr / C.Act = 1 )

Configuration level

Configuration examples

44

KS 90-1

p / KS 92-1

p

InH.1

InL.1

SP.LO

SP

SP.Hi

100%

0%

SH

Out.1Â

InP.1Ê

setpoint

output

process value

SH