background image

4.3 KS90-1 cooling functions

With these controllers, configuration parameter

CYCL (ConF/ Cntr/ CYCL)

can be used for matching the cycle time of 2-point and 3-point controllers. Selec-
tion between “standard” (

CyCl= 0) and “with constant cycle” (CyCl= 3) is

possible.

4.3.1 Standard (

CyCl= 0 )

The adjusted cycle times

t1 and t2 are valid for 50% or -50% correcting vari-

able. With very small or very high values, the effective cycle time is extended to
prevent unreasonably short on and off pulses. The shortest pulses result from ¼
x

t1 or ¼ x t2. The characteristic curve is also called “bath tub curve”

Parameters to be adjusted:

t1 :min. cycle time 1 (heating) [s]

(

PArA/ Cntr)

t2 : min. cycle time 2 (cooling) [s]

4.3.2 Heating and cooling with constant period (

CyCl= 3 )

1 and

t2 are met in the overall out-

put range . To prevent unreasonably
short pulses, parameter

tp is used

for adjusting the shortest pulse dura-
tion. With small correcting values
which require a pulse shorter than the
value adjusted in

tp, this pulse is

suppressed. However, the controller
stores the pulse and totalizes further
pulses, until a pulse of duration

tp

can be output.

Parameters to be adjusted:

t1 : Min. cycle time 1 (heating) [s]

(

PArA/ Cntr)

t2 : min. cycle time 2 (cooling) [s]

tp:

min. pulse length [s]

Configuration level

KS 90-1

p / KS 92-1

p

43

KS90-1 cooling functions

0,0

1,0

2,0

3,0

4,0

5,0

6,0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

Controller output [%]

relative

cycle

duration

T / T

1

t1

2 x

t1

3 x

t1

4 x

t1

50%

50%

t1 t2

/

tp

tp

30%

70%

20%

80%

10%

90%

t1 t2

/