5.3 Input scaling

When using current, voltage or resistance signals as input variables for

InP.1,

InP.2 or/and InP.3 scaling of input and display values at parameter setting
level is required. Specification of the input value for lower and higher scaling
point is in the relevant electrical unit (mA/V/

W).

5.3.1 Input

Inp.1 and InP.3

g

Parameters

InL.x , OuL.x, InH.x and OuH.x are only visible if

ConF / InP.x / Corr = 3 is chosen.
In addition to these settings,

InL.x and InH.x can be adjusted in the range

(0...20mA / 0...10V/

W) determined by selection of S.tYP .

a

For using the predetermined scaling with thermocouple and resistance
thermometer (Pt100), the settings for

InL.x and OuL.x and for InH.x and

OuH.x must have the same value.

g

Input scaling changes at calibration level (r page 56) are displayed by input
scaling at parameter setting level. After calibration reset (

OFF), the scaling

parameters are reset to default.

5.3.2 Input

InP.2

In addition to these settings,

InL.2 and InH.2 can be adjusted in the range

(0...20/ 50mA/

W) determined by selection of S.tYP.

Parameter setting level

KS 90-1

p / KS 92-1

p

55

Input scaling

mA/V

phys.

quantity

mA / V

phys. quantity

OuH.x

OuL.x

InH.x

InL.x

S.tYP

Input signal

InL.x

OuL.x

InH.x

OuH.x

30 (0...20mA)

0 … 20 mA

0

any

20

any

4 … 20 mA

4

any

20

any

40 (0...10V)

0 … 10 V

0

any

10

any

2 … 10 V

2

any

10

any

S.tYP

Input signal

InL.2

OuL.2

InH.2

OuH.2

30

0 … 20 mA

0

any

20

any

31

0 … 50 mA

0

any

50

any