3.6 Manual self-tuning

The optimization aid should be used with units on which the control parameters
shall be set without self-tuning.
For this, the response of process variable x after a step change of correcting vari-
able y can be used. Frequently, plotting the complete response curve (0 to 100%)
is not possible, because the process must be kept within defined limits. Values T

g

and x

max

(step change from 0 to 100 %) or

Dt and Dx (partial step response) can

be used to determine the maximum rate of increase v

max

.

The control parameters can be determined from the values calculated for delay
time T

u

, maximum rate of increase v

max

, control range X

h

and characteristic K ac-

cording to the formulas given below. Increase Xp, if line-out to the set-point os-
cillates.

Operation

KS 90-1

p / KS 92-1

p

23

Manual self-tuning

Tu

Tg

t

x

y

100%

0%

t

Yh

Xmax

{X

{t

y

=

correcting variable

Y

h

=

control range

Tu

=

delay time (s)

Tg

=

recovery time (s)

X

max

=

maximum process value

V

max

=

Xmax

Tg

=

{

{

x

t

= max. rate of

increase of process value