Page 53: Par.2, Setp, 2 parameters, Second parameterset, Parameter setting level

Advertising
background image

5.2 Parameters

Parameter setting level

KS 90-1

p / KS 92-1

p

53

Parameters

q

Cntr

Name

Value range Description

Default

Pb1

1...9999 1

Proportional band 1 (heating) in phys. dimensions (e.g. °C)

100

Pb2

1...9999 1

Proportional band 2 (cooling) in phys. dimensions (e.g. °C)

100

ti1

0,1...9999

Integral action time 1 (heating) [s]

180

ti2

0,1...9999

Integral action time 2 (cooling) [s]

180

td1

0,1...9999

Derivative action time 1 (heating) [s]

180

td2

0,1...9999

Derivative action time 2 (cooling) [s]

180

t1

0,4...9999

Minimal cycle time 1 (heating) [s]. The minimum impulse is 1/4 x t1

10

t2

0,4...9999

Minimal cycle time 2 (heating) [s]. The minimum impulse is 1/4 x t2

10

SH

0...9999

Neutral zone or switching differential for on-off control [phys. dimensions)

2

Hys.l

0...9999

Switching difference Low signaller [engineering unit]

1

Hys.H

0...9999

Switching difference High signaller [engineering unit]

1

d.SP

-1999...9999

Trigger point seperation for additional contact

D/Y/Off[phys.dimensions]

100

tP

0,1...9999

Minimum impulse [s]

OFF

tt

3...9999

Motor travel time [s]

60

Y.Lo

-120...120

Lower output limit [%]

0

Y.Hi

-120...120

Upper output limit [%]

100

Y2

-100...100

2. correcting variable

0

Y.0

-100...100

Working point for the correcting variable [%]

0

Ym.H

-100...100

Limitation of the mean value Ym [%]

5

L.Ym

0...9999

Max. deviation xw at the start of mean value calculation [phys. dimensions]

8

E.H2O

-1999...9999

Min. temperature for water cooling. Below set temperature no water

cooling happens

0

t.on

0,1...9999

Impulse lenght for water cooling. Fixed for all values of controller

output.The pause time is varied.

1

t.oFF

1...9999

Min. pause time for water cooling. The max. effective controller out-

put results from

t.on/(t.on+t.off)·100%

10

F.H2O

0,1...9999

Modification of the (non-linear) water cooling characteristic (see page 41)

1

oFFS

-120...120

Zero offset

0

q

PAr.2

(second parameterset

r

5.4)

Name

Value range Description

Default

Pb12

1...9999 1

Proportional band 1 (heating) in phys. dimensions (e.g. °C), 2. parameter set

100

Pb22

1...9999 1

Proportional band 2 (cooling) in phys. dimensions (e.g. °C), 2. parameter set

100

Ti22

0,1...9999

Integral action time 2 (cooling) [s], 2. parameter set

10

Ti12

0,1...9999

Integral action time 1 (heating) [s], 2. parameter set

10

Td12

0,1...9999

Derivative action time 1 (heating) [s], 2. parameter set

10

Td22

0,1...9999

Derivative action time 2 (cooling) [s], 2. parameter set

10

q

SEtP

Name

Value range Description

Default

SP.LO

-1999...9999

Set-point limit low for Weff

0

SP.Hi

-1999...9999

Set-point limit high for Weff

900

SP.2

-1999...9999

Set-point 2.

0

r.SP

0...9999

Set-point gradient [/min]

OFF

SP

-1999...9999

Set-point (only visible with BlueControl!)

0

SP.LO and SP.Hi should be within the limits of rnGH and rnGL see configura-
tion r Controller page