Configuration 31, Inp.2, Configuration level – West Control Solutions KS 92-1 Programmer manual User Manual

Page 31

Advertising
background image

Configuration level

KS 90-1

p / KS 92-1

p

31

Configuration parameters

Name

Value range Description

Default

20

Pt100 (-200.0 ... 100,0 °C)

( -200,0 ... 150,0°C with reduced lead resistance: measuring resis-

tance + lead resistance ß160 [ )

21

Pt100 (-200.0 ... 850,0 °C)

22

Pt1000 (-200.0 ... 850.0 °C)

23

special 0...4500 Ohm (preset to KTY11-6)

24

special 0...450 Ohm

30

0...20mA / 4...20mA 1

40

0...10V / 2...10V 1

41

special -2,5...115 mV 1

42

special -25...1150 mV 1

50

potentiometer 0...160 Ohm 1

51

potentiometer 0...450 Ohm 1

52

potentiometer 0...1600 Ohm 1

53

potentiometer 0...4500 Ohm 1

S.Lin

Linearization (only at

S.tYP=23(KTY11-6), 24 (0...450W),30

(0..20mA), 40 (0..10V), 41 (0...100mV) and 42 (special -25...1150 mV))

0

0

none

1

Linearization to specification. Creation of linearization table with

BlueControl (engineering tool) possible. The characteristic for

KTY 11-6 temperature sensors is preset.

Corr

Measured value correction / scaling

0

0

Without scaling

1

Offset correction ((controller offset adjustment is at

CALlevel) )

2

2-point correction (calibration is at the controller

CALlevel )

3

Scaling (at

PArA level)

In.f

-1999...9999

Alternative value for error at INP1

If a value is adjusted, this value is used for display and calculation

in case of error (e.g. FAIL).

a

Before activating a substitute value, the effect in the

control loop should be considered!

OFF

fAI1

Forcing INP1 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

1 with current and voltage input signals, scaling is required (see chapter 5.3)

q

InP.2

Name

Value range Description

Default

I.Fnc

Function selection of INP2

1

0

no function (subsequent input data are skipped)

1

heating current input

2

external set-point (

SP.E)

3

Yp input

4

Second process value X2

5

External positioning value Y.E (switch-over r

LOGI / Y.E)

6

no controller input (e.g. transmitter input instead)

7

Process value x1