3.5.6 Optimization at the set-point

Conditions:

w A sufficient set-point reserve is not provided at self-tuning start (see page 17).

w tunE is 0 or 1

w With Strt = 1 configured and detection of a process value oscillation by

more than

± 0,5% of (rnG.H - rnG.L) by the controller, the control

parameters are preset for process stabilization and the controller realizes an
optimization at the set-point (see figure “Optimization at the set-point”).

w when the step attempt after power-on has failed

w with active gradient function ( PArA/ SETP/ r.SP¹ OFF), the set-point

gradient is started from the process value and there isn't a sufficient set-point
reserve.

Optimization-at-the-set-point procedure:
The controller uses its instantaneous parameters for control to the set-point. In
lined out condition, the controller makes a pulse attempt. This pulse reduces the
correcting variable by max. 20% 1, to generate a slight process value under-
shoot. The changing process is analyzed and the parameters thus calculated are
recorded in the controller. The optimized parameters are used for line-out to the
set-point.

With a 3-point controller, optimization for the “heating“ or “cooling” parameters
occurs dependent of the instantaneous condition.
These two optimizations must be started separately.
1 If the correcting variable is too low for reduction in lined out condition it is
increased by max. 20%.