3.5.8 Self-tuning start

Start condition:

w For process evaluation, a stable condition is required. Therefore, the

controller waits until the process has reached a stable condition after
self-tuning start.
The rest condition is considered being reached, when the process value
oscillation is smaller than

± 0,5% of (rnG.H - rnG.L).

w For self-tuning start after start-up, a 10% difference from (SP.LO ... SP.Hi)

is required.

g

Self-tuning start can be blocked via BlueControl

®

(engineering tool) (

P.Loc).

Strt = 0

Only manual start by pressing keys Ù and È
simultaneously or via interface is possible.

Strt = 1

Manual start by press keys Ù and È simultaneously
via interface and automatic start after power-on and detection
of process oscillations.

Operation

Self-tuning

20

KS 90-1

p / KS 92-1

p

Ada LED status

Signification

blinks

Waiting, until process calms down

lit

Self-tuning is running

off

Self-tuning not activ

or ended

1200

1199

°C

°F

SP.2

SP.E

para

func

Ada

Err