2-point correction (

ConF/ InP.1 / Corr = 2):

InL.1: The input value of the lower scaling point is displayed.

The operator must adjust the lower input value by means of a
process value simulator and confirm the input value by pressing key Ù.

OuL.1: The display value of the lower scaling point is displayed.

Before calibration,

OuL.1 equals InL.1.

The operator can correct the lower display value by pressing the ÈÌ
keys. Subsequently, he confirms the display value by pressing key Ù.

InH.1: The input value of the upper scaling point is displayed. .

The operator must adjust the upper input value by means of the
process value simulator and confirm the input value by pressing key Ù.

OuH.1: The display value of the upper scaling point is displayed.

Before calibration

OuH.1 equals InH.1.

The operator can correct the upper display value by pressing keys ÈÌ
Subsequently, he confirms the display value by pressing key Ù.

g

The parameters (

OuL.1, OuH.1) changed at CAL level can be reset by adjusting

the parameters below the lowest adjustment value (

OFF) by means of decrement

key Ì .

Calibration level

58

KS 90-1

p / KS 92-1

p

1200

1199

°C

°F

SP.2

SP.E

para

func

Ada

Err

r

М

Щ

3 sec.

r

PArA

CAL

r Ùr

InP.1

Ù

r

r

r Щ

Щ

InL.1

È

InL1

Ù

OuL.1

r Щ

М

И

r Ù

InH.1

È

InH.1

Ù

OuH.1

r Щ

М

И

ConF

r

Ì

r

М

И

InP.2

InP.3

М

И

End

М

И