2 2-point controller (inverse) 45, Point controller 45 – West Control Solutions KS 92-1 Programmer manual User Manual

Page 45

Advertising
background image

4.4.2 2-point controller (inverse)

ConF / Cntr: SP.Fn = 0

set-point controller

C.Fnc = 1

2-point controller (PID)

C.Act = 0

inverse action
(e.g. heating applications)

ConF / Out.1: O.Act = 0

action

Out.1 direct

Y.1

=

1

control output Y1 active

PArA / Cntr: Pb1

= 1...9999

proportional band 1 (heating)
in units of phys. quantity (e.g. °C)

ti1

= 0,1...9999

integral time 1 (heating) in sec.

td1

= 0,1...9999

derivative time 1 (heating) in sec.

t1

= 0,4...9999

min. cycle time 1 (heating)

PArA / SEtP: SP.LO = -1999...9999 set-point limit low for Weff

SP.Hi = -1999...9999 set-point limit high for Weff

g

For direct action, the controller action must be changed
(

ConF / Cntr / C.Act = 1 ).

Configuration level

KS 90-1

p / KS 92-1

p

45

Configuration examples

InH.1

InL.1

SP.LO

SP

SP.Hi

Out.1Â

InP.1Ê

100%

0%

PB1

setpoint

output

process value

Advertising
This manual is related to the following products: