Technical data 76, Certifications 76, Environmental conditions 76 – West Control Solutions KS 92-1 Programmer manual User Manual

Page 76: Safety test 76, Technical data

Advertising
background image

UNIVERSAL SUPPLY 24 V UC

AC voltage:

20,4...26,4 V AC

Frequency:

48...62 Hz

DC voltage:

18...31 V DC class 2

Power consumption:

approx.. 10 VA

BEHAVIOUR WITH POWER FAILURE

Configuration, parameters and adjusted
set-points, control mode:
Non-volatile storage in EEPROM

BLUEPORT FRONT INTERFACE

Connection of PC via PC adapter (see "Acces-
sory equipment"). The BlueControl software is
used to configure, set parameters and operate
the device.

BUS INTERFACE (OPTION)

Galvanically isolated
Physical:

RS 422/485

Protocol:

Modbus RTU

Transmission speed: 2400, 4800, 9600, 19.200
bits/sec
Address range:

1...247

Number of controllers per bus:

32

Repeaters must be used to connect a higher number
of controllers.

ENVIRONMENTAL CONDITIONS

Protection modes

Front panel:

IP 65 (NEMA 4X)

Housing:

IP 20

Terminals:

IP 00

Permissible temperatures

For specified
accuracy:

0...60°C

Warm-up time:

≥ 15 minutes

For operation:

-20...65°C

For storage:

-40...70°C

Humidity

75% yearly average, no condensation

Altitude

To 2000 m above sea level

Shock and vibration

Vibration test Fc (DIN 68-2-6)

Frequency:

10...150 Hz

Unit in operation:

1g or 0,075 mm

Unit not in operation: 2g or 0,15 mm

Shock test Ea (DIN IEC 68-2-27)

Shock:

15g

Duration:

11ms

Electromagnetic compatibility

Complies with EN 61 326-1
(for continuous, non-attended operation)

GENERAL

Housing

Material:

Makrolon 9415 flame-retardant

Flammability class: UL 94 VO, self-extinguishing

Plug-in module, inserted from the front

Safety test

Complies with EN 61010-1 (VDE 0411-1):
Overvoltage category II
Contamination class 2
Working voltage range 300 V
Protection class II

Certifications

cULus-certification

(Type 1, indoor use)
File: E 208286

Electrical connections

w

flat-pin terminals 1 x 6,3mm or 2 x 2,8mm to
DIN 46 244 or

w

screw terminals for 0,5 to

2,5mm²

On instruments with screw terminals, the
insulation must be stripped by min. 12 mm.
Choose end crimps accordingly.

Technical data

76

KS 90-1