5.4.2

Display line 2

The value to be displayed continuously in the second LCD line can be selected via the BlueControl

Ò

engineering

tool.
As default, the adjusted engineering unit is displayed.

1

Engineering unit as default setting

2

Display of output OUT3 in % (with
corresponding scaling)

g

The values in display line 2 can only be displayed, but not changed.

g

Reset to display of the engineering unit is possible by deleting the entry for line 2..

g

With faulty input values, signals dependent on the inputs (e.g. Inp1, Inp2, display value, Out3) also
indicate FAIL.

5.4.3

Switching over by means of the Enter key

By pressing key Enter, various values can be indicated on display line 2.

w

1

Display of the defined display line 2 value
(via BlueControl

®

);

Limit value LC is set by default

w

2

Display of the error list, if it includes entries.
With several inputs, the following value is

displayed when pressing the Enter key.

w

3

Display of the extended operating level, if
entries were made. With several inputs, the

following value is displayed when pressing the
enter key.

w

4

Return to the initial display
Unless a key is pressed during 30 s, the

instrument returns to the initial display.

Operation

16

Operating level

UNIFLEX CI 45

1 2 F

E

450.3

ыC

дььь

1 2 F

E

450.3

55.0

дььь

1

2

1 2 F E

278.3

°C

дььд

1

2

1 2 F E

278.3

FbF.1

дььд

3

ф

ф

ф

1 2 F E

278.3

L.1

дььдь

4

ф

1 2 F E

278.3

°C

дььд

ф