Technical Data

INPUTS

UNIVERSAL INPUT INP1

Resolution:

>15 bits

Decimal point:

0 to 3 decimals

Digital input filter:

adjustable 0.0...999.9 s

Scanning cycle:

100 ms

Linearization:

31 segments, adaptable with BlueControl®

Measurement value correction: 2-point or offset
Limiting frequency:

1.7 Hz

Thermocouples (Table 1)

Input resistance:

³ 1 MW

Influence of source resistance:

1 µV/

W

Input circuit monitor:

break, polarity

Cold-junction compensation

- Iinternal,

- additional error:

typ.:

max.:

ß_ 0,5 K
ß +1,2 K

External:
- value setting:

0 ...100 °C

-measured via

INP2 (option)

Break monitoring

Sensor current:

ß 1 µA

Operating sense configurable

Resistance thermometer (Table 2)

Connection technique:

3 or 4-wire

Lead resistance:

max. 30

W

Input circuit monitoring:

break and short circuit

Measurement span

The BlueControl® software enables the internal characteristic
curve for the KTY 11-6 temperature sensor to be adapted.
Divided into ranges
Physical measurement range:

0...4500

W

Current and voltage measurement
(Table 3)

Span start and span:

anywhere within the
measurement range

Scaling:

freely selectable –1999...9999

Input circuit monitoring (current): 12.5% below span start (2 mA)

O

2

-measurement (optional)

EMI-measuring by means of INP1 (high-impedance mV-inputs)
suitable for probes with
-constant sensor temperature (heated probes), setting by means
of parameter
- -measured sensor temperature (non-heated probes), measuring

by means of INP2

ADDITIONAL INPUT INP2
(UNIVERSAL, OPTION)

Resolution:

> 15 bits

dig. input filter:

adjustable 0,0...999,9 s

Scanning cycle:

140 ms

Linearization:

as for INP1

Meas. value correction:

2-point or offset correction

Type:

single ended except thermocouples

Technical Data

54

UNIFLEX CI 45

Thermocouple type

Measurement range

Error

Typical resol.

L

Fe-CuNi (DIN)

-100...900°C

-148...1652°F

ß 2K

0.05 K

J

Fe-CuNi

-100...1200°C

-148...2192°F

ß 2K

0.05 K

K

NiCr-Ni

-100...1350°C

-148...2462°F

ß 2K

0.1 K

N

Nicrosil/Nisil

-100...1300°C

-148...2372°F

ß 2K

0.1 K

S

PtRh-Pt 10%

0...1760°C

32...3200°F

ß 3K

0.1 K

R

PtRh-Pt 13%

0...1760°C

32...3200°F

ß 3K

0.1 K

T

Cu-CuNi

-200...400°C

-328...752°F

ß 2K

0.03 K

C

W5%Re-W26%Re

0...2315°C

32...4199°F

ß 3K

0.2 K

D

W3%Re-W25%Re

0...2315°C

32...4199°F

ß 3K

0.2 K

E

NiCr-CuNi

-100...1000°C

-148...1832°F

ß 2K

0.05 K

B *

PtRh-Pt6%

0(400)...1820°C

32(752)...3308°F

ß 3K

0.2 K

Special

-25 … 75 mV

ß 0.1%

0.005%

* Values apply from 400°C upwards.

Table 1: Thermocouple input