Function selection Func

Name

Value range

Description

Fnc.1

Function 1

µ

0

Process value = INP1

2

Difference (INP1 -INP2)

3

Max (INP1, INP2)

4

Min (INP1, INP2)

5

Mean value (INP1, INP2)

6

Switch-over (INP1, INP2)

7

O

2

-Function with constant probe temperature

8

O

2

-Function with measured probe temperature

9

Counter / frequency

10

Process value = INP1 ( TC of INP2)

Fnc.2

Function 2

0

No function

1

Squarer

2

Square root

Fnc.3

Function 3

µ

0

No function

1

Tare

2

Sample & Hold

Inputs InP.1 and InP.2 (

µ)

Name

Value range

Description

I.Fnc

Input function (

µ with 2nd universal input only )

0

No measurement

1

measurement

S.tYP

Sensor type

0

Thermocouple type L (-100...900°C), Fe-CuNi DIN

1

Thermocouple type J (-100...1200°C), Fe-CuNi

2

Thermocouple type K (-100...1350°C), NiCr-Ni

3

Thermocouple type N (-100...1300°C), Nicrosil-Nisil

4

Thermocouple type S (0...1760°C), PtRh-Pt10%

5

Thermocouple type R (0...1760°C), PtRh-Pt13%

6

Thermocouple type T (-200...400°C), Cu-CuNi

7

Thermocouple type C (0...2315°C), W5%Re-W26%Re

8

Thermocouple type D (0...2315°C), W3%Re-W25%Re

9

Thermocouple type E (-100...1000°C), NiCr-CuNi

10

Thermocouple type B (0/100...1820°C), PtRh-Pt6%

18

Special thermocouple (linearization necessary)

20

Pt100 (-200.0 ... 100,0 °C) (150°C with reduced lead resistance)

21

Pt100 (-200.0 ... 850,0 °C)

22

Pt1000 (-200.0...850.0 °C)

23

Special 0...4500 Ohm (preset KTY11-6)