9.1

Offset correction

Offset correction shifts the input value by a pre-defined value.
Parameter setting:

(

ConF/ InP/ Corr =1 ):

w

On-line offset correction at the process is possible.

InL:

The actual input value of the scaling point is displayed.
The correction function is activated by means of keys ÈÌ ; the display changes from Off to
the measured value.
The operator must wait, until the process is at rest.
Subsequently, the input value has to be confirmed by pressing key ô .

OuL:

The scaling point display value is indicated.
The operator can correct the display value by pressing keys ÈÌ. Subsequently, he presses key

ô to confirm the display value.

Calibrating level

50

Offset correction

UNIFLEX CI 45

r

3 sec.

r

PArA

CAL

r

r

InP

r

InL

r

r

OuL

r

End

r

ConF

rr

InL

r

450.3

450.0

дььь

ф

ф

ф

ф

ф

ф

ф

X

standard setting

offset correction

InL

OuL

new

display

OuL

old