O.src, O.fai, Di.fn – West Control Solutions CI 45 User Manual

Page 43: Err.r, I.chg

Advertising
background image

Name

Value range

Description

O.Src

Signal source for analog output OUT3 (only visible with O.TYP=1..4 )

0

Not active

3

Process value

7

Measured value INP1

8

Measured value INP2

µ

O.FAI

Fail behaviour

0

Upscale

1

Downscale

Inf.1

Status message Inf.1 (operating hours) (visible only with BlueControl!)

0

Not active

1

Active

Inf.2

Status message Inf.2 (number of switching cycles) (visible only with BlueControl!)

0

Not active

1

Active

fOut

Forcing OUT3 (only visible with BlueControl!)

0

Not active

1

The value for this output is preset via interface

Logic LOGI

Name

Value range Description

di.Fn

Function of inputs (valid for all inputs)

0

Direct

1

Invers

2

toggle key function (adjustable for 2-point-operation with interface and di1)

L_r

Local / remote switchover
(Remote: Adjustment of all values via the front panel is blocked)

0

No function (switch-over via interface is possible)

1

Always active.

2

Di1 switches.

7

Limit 1 switches

8

Limit 2 switches

9

Limit 3 switches

Err.r

Source for resetting all stored entries in the error list

0

No function (switch-over via interface is possible)

2

Di1 switches.

7

Limit 1 switches

8

Limit 2 switches

9

Limit 3 switches

I.ChG

Switching the effective process value between INP1 and INP2.
µ (input 2 must be released (CONF / Inp.2 / I.Fnc = 1))

0

No function (switch-over via interface is possible).

2

Di1 switches.

7

Limit 1 switches

8

Limit 2 switches

9

Limit 3 switches

Configuration level

UNIFLEX CI 45

Configurations