Latched alarms Lim1/2/3 (E element displayed) can be acknowledged, i.e. reset via digital alarm di1.

For Configuration, see page 46:

ConF / LOGI / Err.r

g

When an alarm is still pending, i.e. unless the error cause was removed ( E display blinks), latched alarms
cannot be acknowledged and reset.

g

If sensor errors should not be on the error list any more after error correction without manual reset in the
error list, suppression via BlueControl is possible by means of setting ILat.

CONF / othr / ILat

1

blocked

This setting is without effect on limit values Lim.1 … 3 configured for storage.

6.17

Reset to factory setting

In case of faulty configuration, UNIFLEX CI 45 can
be reset to its factory setting.

Ü

For this, the operator must keep the keys
increment and decrement pressed during
power-on.

*

For confirmation, press key increment to
select YES

Ö

Confirm factory resetting with Enter and the
copy procedure isl started (display

COPY).

ä

Afterwards the device restarts.

In all other cases, no reset will occur(timeout
abortion).

g

If one of the operating levels was blocked,
reset to factory setting is not possible.

g

If a pass number was defined (via
BlueControl

®

) but no operating level was

blocked, enter the correct pass number
when prompted in

3. A wrong pass numbers

aborts the reset action.

g

The copy procedure (

COPY) can take some

seconds.

Now, the transmitter is in normal operation.

Functions

UNIFLEX CI 45

Reset to factory setting

37

Error-state

Signification

2

Pending error

Change to error status

1after error removal

1

Stored error

Change to error status 0 after acknowledgement in error list

0

0

no error/message

Not visible, except during acknowledgement