Frequency output

Output by means of voltage output

Frequency range:

0, 0.25 ...1000 Hz (square-wave signal)

Output value:

scalable

Level:

0 / 11,5V

Pulse output

by means of integrator with automatic resetting

Frequency range:

0 ...5 Hz
(max. 5 pulses/s)

Pulse duration:

100 ms (INP1 measurement)
140 ms (INP1 + INP2 measurement)

Galvanic isolation

permissible voltages:

safety isolation

ß 300 Vrmsf AC against earth

functional isolation

ß 30 Vrmsf AC against earth

Galvanic isolation of inputs, outputs and supply voltage

Test voltages:

Between power supply and in-/outputs:

2,3 kV AC, 1 min

Between input and output:

500 V AC; 1min

Max. permissible voltages:

Between inputs/outputs against earth:

ß 33 V AC

POWER SUPPLY

Depending on ordered version

AC supply

Voltage:

90...260 V AC

Frequency:

48...62 Hz

Consumption:

approx. 7 VA max.

Universal supply 24 V UC

AC supply:

18...30 V AC

Frequency:

48...62 Hz

DC supply:

18...31 V DC

Consumption:

approx. 3 VA / W max.

Supply only from safety electrical low voltage (SELV).
* Instruments with optional system interface:
Energization via the bus connector of field bus coupler or power
supply module

Behaviour with power failure

Configuration and parameter settings:
Permanent storage in EEPROM

BLUEPORT

®

FRONT INTERFACE

Connection to the transmitter front via a PC adapter (see
‘Accessories’). The BlueControl

®

software enables the CI 45 to be

configured, parameters set, and operated.

BUS INTERFACE (OPTIONAL)

RS 485

Connection via bus connector fitted in the top-hat rail. Screened
cables should be used.
Galvanically isolated
Type:

RS 485

Transmission speed:

2400, 4800, 9600, 19.200,
38.400 bits/sec

Parity:

even, uneven, none

Address range:

1...247

Number of transmitters per bus segment:

32

Protocol

Modbus RTU

SYSTEM INTERFACE

For connection to field bus coupler (s. system components)
Connection via bus connector in the top-hat rail.

ENVIRONMENTAL CONDITIONS

Protection mode

Front panel:

IP 20

Housing:

IP 20

Terminals:

IP 20

Technical Data

UNIFLEX CI 45

57

RS 485

power

relay 1
relay 2

input 1

di1 (contact)

output 3

safety isolation

functional isolation

front interface

Fig. 1: Galvanic isolation