Fnc.1 (fnc.2) (fnc.3), Src.1 (src.2) (src.3), O.act – West Control Solutions CI 45 User Manual

Page 41: Lim.1, Lim.2, Lim.3, Fai.1, Fai.2, Fai.f, Sb.er

Advertising
background image

Limit values Lim1 … Lim3

Name

Value range

Description

Fnc.1

(Fnc.2)
(Fnc.3)

Function of limit 1 (2, 3)

0

Switched off

1

Measured value monitoring

2

Measured value monitoring + alarm status latch. A stored limit value can
be reset via error list or a digital input ( -> LOGI/Err.r)

3

Signal change (in minutes).

4

Signal monitoring for rate of change (per minute) + storage of the alarm
status. A stored limit value can be reset via error list or a digital input (
->LOGI/Err.r)

Src.1

(Src.2)
(Src.3)

Source of limit 1 (2, 3)

0

Process value= displayed value

3

Measured value of the analog input INP1

4

Measured value of the analog input INP2

10

Counter/frequency measurement value

C.Std

OFF; 1 … 9999999

Monitoring operating hour (only visible with BlueControl!)

C.Sch

OFF; 1 … 9999999

Monitoring duty cycle (only visible with BlueControl!)

Outputs Out.1 and Out.2

µ (Relay)

Name

Value range

Description

O.Act

Direction of operation OUT1

0

Direct / normally open

1

Inverse / normally closed

Lim.1

Signal limit 1

0

Not active

1

Active

Lim.2

Signal limit 2

0

Not active

1

Active

Lim.3

Signal limit 3

0

Not active

1

Active

FAi.1

Signal INP1 fail

0

Not active

1

Active

FAi.2

Signal INP1 fail

µ

0

Not active

1

Active

FAi.F

Frequency error µ message

0

Not active

1

Active

Sb.Er

System bus error µ message

0

Not active

1

Active

fOut

Forcing of analog output OUT 1 (only visible with BlueControl!)

0

Not active

1

The value for this output is preset via interface

Inf.1

Status message Inf.1 (operating hours) (only visible with BlueControl!)

0

Not active

1

active

Configuration level

UNIFLEX CI 45

Configurations

41