Mounting 8, Dismounting 8, Mounting 8 - 9 – West Control Solutions CI 45 User Manual

Page 8: Mounting, Abmessungen / dimensions

Advertising
background image

.

3

Mounting

The unit is provided for vertical mounting on 35 mm top-hat rails to EN 50022.

If possible, the place of installation should be exempt of vibration, aggressive media (e.g. acid, lye), liquid, dust or
aerosol.

The instruments of the rail line series can be mounted directly side by side. For mounting and dismounting, min. 8 cm
free space above and below the units should be provided.

For mounting, simply clip the unit onto the top-hat rail from top and click it in position.
To dismount the unit, pull the bottom catch down using a screwdriver and remove the unit upwards.

g

Transmitter CI 45 does not contain any maintenance parts, i.e. the unit need not be opened by the
customer.

a

The unit may be operated only in environments for which it is suitable due to its protection type.

a

The housing ventilation slots must not be covered.

a

In plants where transient voltage peaks are susceptible to occur, the instruments must be equipped with
additional protective filters or voltage limiters!

l

Caution! The instrument contains electrostatically sensitive components .

a

Please, follow the instructions given in the safety hints.

a

To maintain contamination degree 2 acc. to EN 61010-1, the instrument must not be installed below
contactors or similar units from which conducting dust or particles might trickle down.

- preliminary -

Mounting

UNIFLEX CI 45

8

%

max.
95% rel.

max.

55°C

-10°C

min.

22.5

(0,87”)

117.5 (4,63”)

99

(3,90”)

2.3

111 (4,37”)

5.5

(0,08”)

(0,20”)

click

Montage / mounting

Abmessungen / dimensions