6.14.1

Measured value monitoring

g

The signal to be monitored can be selected separately for each alarm in the configuration. The following
signals are available:

Process value (display value)

Measurement value INP1

Measurement value INP2 (option)

Counter / frequency measurement value (optional)

Each of the 3 limit values

Lim.1 … Lim.3 has 2 trigger points H.x (Max) and L.x (Min), which can be switched off

individually (parameter = “

OFF”). The hysteresis HYS.x of each limit value is adjustable.

Input value monitoring

Input value monitoring is as shown below:

Display range

Limit value 1

Outputs

Display range

Limit value 1

Outputs

Display range

Limit value 1

Outputs

Normally open: (

ConF / Out.x / O.Act = 0 )

(as shown in the example)

Normally closed:

(

ConF / Out.x / O.Act = 1 )

(inverted output relay action)

Functions

30

Limit value processing

UNIFLEX CI 45

H.1

LED rot / red

HYS.1

-1999

9999

H.1

Operating principle with absolute alarm (ex. Lim.1)

L.1 = OFF

L.1

HYS.1

-1999

9999

LED rot / red

L.1

H.1 = OFF

L.1

LED

LED

HYS.1

HYS.1

H.1

-1999

9999

rot / red

rot / red

L.1

H.1