Scaling

The frequency input value can be scaled to a physical value in two points.
1st value:

– input

Frq.L (value specified in kHz)

– physical value

Ou.L

2nd value:

– input

Frq.H (value specified in kHz)

– physical value

Ou.H

Example:

5 Hz

= 2 l/min

20 Hz

= 30 l/min

Settings:

Frq.L = 0,002;

Ou.L = 5

Frq.H = 0,020;

Ou.H = 30

Filter

The frequency input value can be filtered (Parameter

Frq.F).

Exceeded frequency range

g

When exceeding the frequency input range end, measurements are switched off during approx. 1 s.

Out-of-range signalling is possible via an output signal:

ConF / Out.x / FAi.F = 1

Simulation

A special “Freq” input window is provided for simulation of the frequency input in the BlueControl

®

engineering tool.

It should be specified in kHz.

6.10

Arithmetic functions

The following arithmetic functions are available in configuration setting

CONF / Fnc.2 :

Square function

Formula: x

2

The display value which is squared is output.

Square root extraction

Formula:

Öx

For output, the square root of the display value is extracted.
For values x

£ 0 , value 0 is output.

Functions

UNIFLEX CI 45

Arithmetic functions

27