1 connectors 9, Connectors 9 – West Control Solutions CI 45 User Manual

Page 9

Advertising
background image

3.1

Connectors

The four instrument connectors are of the plug-in type. They plug into the housing from top or bottom and click in
position. Releasing the connectors should be done by means of a screwdriver.
Two connector types are available:

Screw terminals for max. 2,5 mm

2

conductors

Spring-clamp terminals for max. 2,5 mm

2

conductors

g

Before handling the connectors, the unit must be disconnected from the
supply voltage.

Tighten the screw terminals with a torque of 0,5 - 0,6 Nm.

With spring-clamp terminals, stiff and flexible wires with end crimp can be
introduced into the clamping hole directly. For releasing, actuate the (orange)
opening lever.

a

Contact protection: Terminal blocks which are not connected should remain in the socket.

Mounting

UNIFLEX CI 45

Connectors