Positioning, Airflow & maintenance clearances, Positioning 114 airflow & maintenance clearances – Airedale TurboChill FreeCool 200kW - 1830kW User Manual

Page 114: Chillers turbochill™ air cooled and freecool

Advertising
background image

114

Chiller Technical Manual 7525355 V1.1.0_04_2013

In

st

alla

tio

n

Chillers

TurboChill™ Air Cooled and FreeCool

Installation Data

Positioning

The installation position should be selected with the following points in mind:

Position on a stable and even base, levelled to ensure that the compressor operates correctly

Levelling should be to +/- 5mm

Where vibration transmission to the building structure is possible, fit spring anti-vibration mounts and flexible

water connections

Observe airflow and maintenance clearances

Pipe work and electrical connections are readily accessible

Where multiple units are installed, due care should be taken to avoid the discharge air from each unit adversely

affecting other units in the vicinity

Within a side enclosed installation, the fan MUST be higher than the enclosing structure

Increase airflow and maintenance clearances for side-enclosed or multiple unit applications

Ensure there are no obstructions directly above the fans

Allow free space above the fans to prevent air recirculation

Airflow & Maintenance Clearances

Application

Distance from Overall Base Dimension

Single unit

1300mm

Side-enclosed or multiple units

2600mm