95

Chiller Technical Manual 7525355 V1.1.0_04_2013

Te

ch

nic

al

Chillers

TurboChill™ Air Cooled and FreeCool

Fre

eC

oo

l

Sound Data - TCF

TCF - EC Fans

EC Fans

Single Octave Sound Levels (dB)

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall

[dB(A)]

TCF11X08S-07

Power

84

83

81

78

78

73

77

81

85

Pressure @ 10m

52

51

48

45

45

41

45

49

52

TCF11X06L-11

Power

84

83

79

79

82

75

76

80

86

Pressure @ 10m

51

50

47

46

49

43

44

47

53

TCF11X08L-08

Power

85

84

81

79

82

75

76

80

86

Pressure @ 10m

52

51

48

47

49

43

43

47

53

TCF11X10L-10

Power

86

85

82

80

82

75

76

80

86

Pressure @ 10m

53

52

49

47

49

42

43

47

53

TCF12X08S-09

Power

85

84

82

80

80

76

80

84

87

Pressure @ 10m

52

51

49

47

47

43

48

52

55

TCF12X10S-05

Power

86

85

82

80

80

76

80

84

88

Pressure @ 10m

53

52

50

47

47

43

47

51

55

TCF12X12S-05

Power

87

86

83

80

81

76

80

84

88

Pressure @ 10m

53

53

50

47

47

43

47

51

55

TCF12X14S-05

Power

87

86

84

81

81

76

80

84

88

Pressure @ 10m

54

53

50

48

47

43

47

51

55

TCF12X12L-12

Power

87

86

82

82

85

78

79

83

89

Pressure @ 10m

53

53

49

49

52

45

46

50

56

TCF12X14L-12

Power

87

86

83

82

85

78

79

83

89

Pressure @ 10m

54

53

50

49

52

45

46

49

55

TCF12X16L-12

Power

88

87

84

82

85

78

79

83

89

Pressure @ 10m

54

53

50

49

52

45

45

49

55

TCF12X18L-13

Power

88

87

84

83

85

78

79

83

89

Pressure @ 10m

55

54

50

49

51

45

45

49

55

TCF12X20L-13

Power

89

88

85

83

85

78

79

83

89

Pressure @ 10m

55

54

51

49

51

44

45

49

55

(1) dB(A) is the overall sound level, measured on the A scale.
(2) All sound data measured at nominal conditions: Water in/out 16/10°C at 35°C ambient.
(3) Based on standard unit, for units fitted with optional extras, please contact Airedale.