TurboChill™ Air Cooled and FreeCool

Alarms

Code

Description

Auto Reset

Unit Disabled

Component Disabled

Cause

Action

Default Alarm Type

AL078 SCR Temp. Comp.4

Indicates insufficient cooling

to the SCR plate

Check: alarms

limits in the

compressor

1 = Non critical

AL079 System Lockout Comp.4

When a SCR/inverter/cavity

temperature fault occurs more

than 3 time in 30minutes

Check: motor

cooling line and

solenoids valves /

cycle power

1 = Non critical

AL080 Hours Limit Comp.1

The hours run for the

compressor has exceeded the

threshold

If component

is functioning

correctly perform

maintenance and

reset hours

1 = Non critical

AL081 Hours Limit Comp.2

1 = Non critical

AL082 Hours Limit Comp.3

1 = Non critical

AL083 Hours Limit Comp.4

1 = Non critical

AL084 Hours Limit Pump 1

The hours run for the pumps

has exceeded the threshold

If component

is functioning

correctly perform

maintenance and

reset hours

1 = Non critical

AL085 Hours Limit Pump 2

1 = Non critical

AL086 Liquid Level 1 Fault

Circuit 1 liquid level sensor

has gone out of range

Check: the sensor

/ Wiring

1 = Non critical

AL087 CW Valve Feedback

Valve failed to open

Check: valve

operation / Wiring

1 = Non critical

AL088 Cond. Pressure2 Fault

• •

Circuit 2 condensing pressure

sensor has gone out of its

operating range

Check: wiring /

Sensor

1 = Non critical

AL089 Low Pressure 2 Switch

Circuit 2 suction pressure is

below 0.5 bar

Check: refrigerant

charge / EEV

operation

2 = Critical

AL090 High Cond. Pressure 2

Circuit 2 condensing pressure

is higher than 13.6 Bar

Check: Condenser

/ Condenser Fans

1 = Non critical

AL091 Liquid Level 2 Fault

• •

Circuit 2 liquid level sensor

has gone out of range

Check: wiring /

Sensor

1 = Non critical

AL092 Evap.Inlet Temp. Fault

• •

The sensor has gone out of its

operating range

Check: wiring /

sensor

1 = Non critical

AL093 Serious Alarm Comp.1

The compressor has been in

alarm more than 5 times in 2

hours

Check the

operation of the

compressor /

circuit

1 = Non critical

AL094 Serious Alarm Comp.2

1 = Non critical

AL095 Serious Alarm Comp.3

1 = Non critical

AL096 Serious Alarm Comp.4

1 = Non critical

AL097 Evap. Low Flowrate

• •

The evaporator flow rate is

equal to or less than 20% of

design

Check the

evaporator strainer

or for any other

blockages

1 = Non critical

AL098 Liq. Valve EVD1 Alarm

The electronic expansion

valve driver used to position

the flooded evaporator liquid

level control valve is in alarm

Check the wiring

between the EVD

and the liquid

level control

valve / check

the operation of

the control valve

stepper motor

2 = Critical

AL099 Liq. Valve EVD2 Alarm

2 = Critical