Chillers turbochill™ air cooled and freecool, Trou ble sh oo tin g, Alarms – Airedale TurboChill FreeCool 200kW - 1830kW User Manual

Page 135

Advertising
background image

135

Chiller Technical Manual 7525355 V1.1.0_04_2013

Trou

ble

sh

oo

tin

g

Chillers

TurboChill™ Air Cooled and FreeCool

Alarms

Code

Description

Auto Reset

Unit Disabled

Component Disabled

Cause

Action

Default Alarm Type

AL001 Comp1 MB Comms.Offline

Communication to the

compressor has failed

Check: Wiring

/ modbus card

/ compressor

communication

board /

compressor fuses

and power

1 = Non critical

AL002 Comp2 MB Comms.Offline

1 = Non critical

AL003 Comp3 MB Comms.Offline

1 = Non critical

AL004 Comp4 MB Comms.Offline

1 = Non critical

AL005 Power Meter MB Offline

• •

Communication to the power

meter has been lost

Check: wiring /

modbus card /

power meter

1 = Non critical

AL006 Cond. Pressure1 Fault

• •

The sensor has gone out of its

operating range

Check: wiring /

sensor

1 = Non critical

AL007 Evap.Diff.Press. Fault

• •

1 = Non critical

AL008 Evap.Flow Meter Fault

• •

1 = Non critical

AL009 Return Temp. Fault

• •

1 = Non critical

AL010 Supply Temp. Fault

• •

1 = Non critical

AL011 Temp. Setpoint Fault

1 = Non critical

AL012 Cond.Air On Temp Fault

1 = Non critical

AL013 Clock Alarm

The internal clock has

malfunctioned

Replace battery

1 = Non critical

AL014 Phase Failure

• •

The 3 phase power supply

crossed / loss (wait 30s with a

power meter on power up)

Check 3 phase

connection

2 = Critical

AL015 Emergency Stop

• •

The emergency stop button

has been pressed

Release the

emergency stop

button

2 = Critical

AL016 Evaporator Flow Alarm

• •

No evaporator flow has been

detected

Check: pumps are

running / flow

2 = Critical

AL017 Low Pressure 1 Switch

• •

Circuit 1 suction pressure

below 0.5 bar

Check: refrigerant

charge / EEV

operation

2 = Critical

AL018 Comp1 Status Alarm

Contactor has been switched

on but has failed to operate

Check: high

pressure switch /

contactor. / wiring.

1 = Non critical

AL019 Comp2 Status Alarm

1 = Non critical

AL020 Comp3 Status Alarm

1 = Non critical

AL021 Comp4 Status Alarm

1 = Non critical

AL022 Mains Failure

• •

The permanent L4 supply has

failed to the control panel

Check: L4 supply

2 = Critical

AL023 Pump1 Status Alarm

• •

Contactor has been switched

on but has failed to operate

Check: contactor /

wiring

1 = Non critical

AL024 Pump2 Status Alarm

• •

1 = Non critical