ELECTRICAL DATA

TCF11X06S-07

TCF11X08S-07

TCF11X06L-11

Unit Data
Full Load Amps

(1)

A

150

155

225

Maximum Start Amps

A

2

2

2

Mains Supply

VAC

400V (±10%) 3PH 50Hz

Recommended Mains Fuse Size

A

160

200

250

Max Mains Incoming Cable Size (Direct to 3 Phase Mains Isolator)

mm²

2x 300mm² (Torque >20Nm)

Independent Permanent Supply Recommended Fuse Size

A

25

25

251

Independent Permanent Supply

VAC

230V 1PH 50Hz (±10%)

Max Permanent Incoming Cable Size (Direct to Control Panel Isolator)

mm²

6mm² / 8 AWG

Control Circuit

VAC

24 VAC & 230VAC (±10%)

Evaporator
Immersion Heater Rating

W

500 (2x 250)

500 (2x 250)

500 (2x 250)

External Trace Heating
Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)
Quantity

6

8

6

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.3

1.3

1.3

Condenser Fan - Per Fan (EC)
Quantity

6

8

6

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Condenser Fan - Per Fan (EC High Air Volume)
Quantity

6

8

6

Full Load Amps

A

4.8

4.8

4.8

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

3.10

3.10

3.10

Compressor - Per Compressor
Nominal Run Amps

A

135

135

210

Quantity

1

1

1

Motor Rating

kW

87

87

129

Start Amps

A

2

2

2

Type Of Start

Electronic Soft Start

Technical Data

Electrical

TCF11X06S-07, TCF11X08S-07, TCF11X06L-11

(1) Based at full load Conditions and AC Standard Fans

Pump electrical data is avaliable from Airedale upon request.