Chillers turbochill™ air cooled and freecool, Tr ou ble sh oo tin g, Alarms – Airedale TurboChill FreeCool 200kW - 1830kW User Manual

Page 138

Advertising
background image

138

Chiller Technical Manual 7525355 V1.1.0_04_2013

Tr

ou

ble

sh

oo

tin

g

Chillers

TurboChill™ Air Cooled and FreeCool

Code

Description

Auto Reset

Unit Disabled

Component Disabled

Cause

Action

Default Alarm Type

AL060 Suction Press. Comp.3

The suction pressure is too

high / low at the compressor

Check: charge

/ system load /

sensor / suction

strainer

1 = Non critical

AL061 Discharge Press.Comp.3

The discharge pressure has

exceeded it limit

Check: the sensor

/ condenser/ shut

off valves

1 = Non critical

AL062 3Ph. Current Comp.3

Indicates there maybe an

excessive load on the system

1 = Non critical

AL063 Cavity Temp. Comp.3

The cavity temperature inside

the compressor is high

Check: the liquid

cooling line /

solenoid valve

1 = Non critical

AL064 Air/Water Temp. Comp.3

There maybe insufficient

water flow due to air gaps

Check: sensor

limits

1 = Non critical

AL065 Compress. Ratio Comp.3

The compression ratio of the

compressor is out of range

Check: condenser

/ evaporator loads

and settings

1 = Non critical

AL066 Bearing Reset Comp.3

Low suction / liquid

Check: refrigerant

circuit

1 = Non critical

AL067 SCR Temp. Comp.3

Indicates insufficient cooling

to the SCR plate

Check: alarms

limits in the

compressor

1 = Non critical

AL068 System Lockout Comp.3

When a SCR / inverter / cavity

temperature fault occurs more

than 3 time in 30 minutes

Check: motor

cooling line and

solenoids valves /

cycle power

1 = Non critical

AL069 Inverter Temp. Comp.4

The temperature of the

compressor inverter is high

Check: liquid line

to the compressor

/ solenoid valves

1 = Non critical

AL070 Discharge Temp. Comp.4

The temperature of the

discharge gas is high

Check: refrigerant

charge / discharge

temperature

sensor

1 = Non critical

AL071 Suction Press. Comp.4

The suction pressure is too

high / low at the compressor

Check: charge

/ system load /

sensor / suction

strainer

1 = Non critical

AL072 Discharge Press.Comp.4

The discharge pressure has

exceeded it limit

Check: the sensor

/ condenser/ shut

off valves

1 = Non critical

AL073 3Ph. Current Comp.4

Indicates there maybe an

excessive load on the system

1 = Non critical

AL074 Cavity Temp. Comp.4

The cavity temperature inside

the compressor is high

Check: the liquid

cooling line /

solenoid valve

1 = Non critical

AL075 Air/Water Temp. Comp.4

There maybe insufficient

water flow due to air gaps

Check: sensor

limits

1 = Non critical

AL076 Compress. Ratio Comp.4

The compression ratio of the

compressor is out of range

Check: condenser

/ evaporator loads

and settings

1 = Non critical

AL077 Bearing Reset Comp.4

Low suction / liquid

Check: refrigerant

Circuit

1 = Non critical

Alarms