Chiller Technical Manual 7525355 V1.1.0_04_2013

Trou

ble

sh

oo

tin

g

Chillers

TurboChill™ Air Cooled and FreeCool

(1) The water flow is reduced however the differential pressure switch may still remains healthy as the pressure would

increase.

Fault

Possible Cause

Remedy / Action

W

aterside

Pump not operating

No power to pump.

Check isolator, fuses, MCBs, contactor

and control circuit wiring.

Inverter tripped and does not

auto reset (the microprocessor

will try and auto reset 3 times)

Reset inverter drive via microprocessor.

No water flow

Strainer blocked.

Clean strainer

Pump noisy

Air in water system.

Purge air from water system.

Pump cavitations.

Ensure there is 0.5m NPSH suction

head to avoid cavitations.

Unit not operating

due to water pressure

sensor low limit alarm.

Low flow alarm operating.

Check that the low flow pressure

variable is set correctly. If too high the

unit may have nuisance trips.

Low temp limit alarm

Partial blockage in evaporator

causing low flow.(1)

Clean evaporator

No heatload on system

Ensure heatload is avaliable for unit to operate

Water/ Glycol freezing

up (crystallizes)

Insufficient glycol / water concentration

for operating temperatures.

Check glycol concentration and add accordingly.