Service Tools / Test Equipment

Voltmeter

Screwdrivers / Allen Keys

Ammeter

Safety Equipment

Safety Glasses / Goggles

Maintenance

Electrical Inspection

Procedures

Electrical Connections

Ensure all electrical connections are tight and correctly terminated.

Electrical Earthing

Check that the unit is correctly earthed.

Voltage

Measure the voltage at the following points and record on the maintenance sheet:

Voltage at busbar

Dedicated power supply

Voltage at permanent supply

Control voltage at transformer (min 22.5V, max 25V)

The voltage measurements should be carried out with the unit MCB’s turned off.

EC Fan Interrogation

The EC fans can be interrogated by connecting a hardware interface kit from the fan to a PC. The kit comprises of a

USB to RS232 9-pin “D-type” adapter. This should be installed on the PC with the software supplied with the kit.
The “COM” port of the USB to RS232 adapter should be assigned to a free COM port between COM 1 and 4 via the

system device manager.

Connect the RS232 to RS485 interface converter to the USB port of your PC via the USB to RS232 serial interface lead

and connect the RS485 output to the fan.
Tx += RS A

Tx - = RS B

(Except high airflow fans. Interogation is via a separate module avaliable from Airedale)

Task

Frequency

Electrical

Inspection

3 Mths

12 Mths

60 Mths

Check mains power supply voltages

Check electrical terminals are tight.

Check for signs of hot spots/ discolouration on power cables.

Check amperages are as per design.