Chillers turbochill™ air cooled and freecool, Tr ou ble sh oo tin g, Alarms – Airedale TurboChill FreeCool 200kW - 1830kW User Manual

Page 140

Advertising
background image

140

Chiller Technical Manual 7525355 V1.1.0_04_2013

Tr

ou

ble

sh

oo

tin

g

Chillers

TurboChill™ Air Cooled and FreeCool

Alarms

Code

Description

Auto Reset

Unit Disabled

Component Disabled

Cause

Action

Default Alarm Type

AL100 High Liquid Level Cct1

High level of refrigerant in

flooded evaporator

Check the

operation of the

liquid level control

valve

1 = Non critical

AL101 Low Liquid Level Cct1

Low level of refrigerant in

flooded evaporator

Check the

operation of the

liquid level control

valve / refrigerant

leak

1 = Non critical

AL102 High Liquid Level Cct2

High level of refrigerant in

flooded evaporator

Check the

operation of the

liquid level control

valve

1 = Non critical

AL103 Low Liquid Level Cct2

Low level of refrigerant in

flooded evaporator

Check the

operation of the

liquid level control

valve / refrigerant

leak

1 = Non critical

AL104 Cond.Return Temp.Fault

• •

The sensor has gone out of its

operating range

Check: wiring /

sensor

1 = Non critical

AL105 Cond.Supply Temp.Fault

• •

The sensor has gone out of its

operating range

Check: wiring /

sensor

1 = Non critical

AL106 Cond.Diff.Press. Fault

• •

The sensor has gone out of its

operating range

Check: wiring /

sensor

1 = Non critical

AL107 Condenser Flow Alarm

No condenser flow has been

detected

Check: condenser

pump is running

/ flow

2 = Critical

AL108 Unit Pump Down Cct1

The circuit has been partially

pump down and disabled

Check for

refrigerant loss

and reset

2 = Critical

AL109 Unit Pump Down Cct2

2 = Critical

AL110 Possible Unit Ref.Leak

A possible unit refrigerant leak

has been detected

Check for

refrigerant loss

1 = Non critical

AL111 Mains Isolator Status Alarm

• •

Mains isolator is off.

If safe to do so

switch on.

2 = Critical

AL112 Circuit 1 Condenser Fan Trip

One or more condenser fans

have tripped on circuit 1.

Check circuit 1

condenser fan

operation / wiring.

1 = Non critical

AL113 Circuit 2 Condenser Fan Trip

One or more condenser fans

have tripped on circuit 2.

Check circuit 2

condenser fan

operation / wiring.

1 = Non critical

AL114 Condenser Fan Isolator Status

Condenser fan isolator is off.

If safe to do so

switch on.

1 = Non critical

AL115 Pump Isolator Status

Pump isolator is off.

If safe to do so

switch on.

1 = Non critical

AL116

Refrigerant Leak Detector 1 MB

Communications Offline

Communication to the leak

detector has failed

Check: wiring

/ modbus

connection / leak

detector.

1 = Non critical

AL117

Refrigerant Leak Detector 2 MB

Communications Offline

1 = Non critical

AL118

Refrigerant Leak Detector 3 MB

Communications Offline

1 = Non critical

AL119

Refrigerant Leak Detector 4 MB

Communications Offline

1 = Non critical