Chillers turbochill™ air cooled and freecool, Trou ble sh oo tin g, Alarms – Airedale TurboChill FreeCool 200kW - 1830kW User Manual

Page 137

Advertising
background image

137

Chiller Technical Manual 7525355 V1.1.0_04_2013

Trou

ble

sh

oo

tin

g

Chillers

TurboChill™ Air Cooled and FreeCool

Code

Description

Auto Reset

Unit Disabled

Component Disabled

Cause

Action

Default Alarm Type

AL044 Bearing Reset Comp.1

Low suction pressure / liquid Check: refrigerant

circuit

1 = Non critical

AL045 SCR Temp. Comp.1

Indicates insufficient cooling

to the SCR plate

Check: alarms

limits in the

compressor

1 = Non critical

AL046 System Lockout Comp.1

When a SCR / inverter / cavity

temperature fault occurs more

than 3 time in 30minutes

Check: motor

cooling line and

solenoids valves /

cycle compressor

power

1 = Non critical

AL047 Inverter Temp. Comp.2

The temperature of the

compressor inverter is high

Check: liquid line

to the compressor

/ solenoid valves

1 = Non critical

AL048 Discharge Temp. Comp.2

The temperature of the

discharge gas is high

Check: refrigerant

charge / discharge

temperature

sensor

1 = Non critical

AL049 Suction Press. Comp.2

The suction pressure is too

high / low at the compressor

Check: charge

/ system load /

sensor / suction

strainer

1 = Non critical

AL050 Discharge Press.Comp.2

The discharge pressure has

exceeded it limit

Check: the sensor

/ condenser/ shut

off valves

1 = Non critical

AL051 3Ph. Current Comp.2

Indicates there maybe an

excessive load on the system

1 = Non critical

AL052 Cavity Temp. Comp.2

The cavity temperature inside

the compressor is high

Check: the liquid

cooling line /

solenoid valve

1 = Non critical

AL053 Air/Water Temp. Comp.2

There maybe insufficient

water flow due to air gaps

Check: sensor

limits

1 = Non critical

AL054 Compress. Ratio Comp.2

The compression ratio of the

compressor is out of range

Check: condenser

/ evaporator loads

and settings

1 = Non critical

AL055 Bearing Reset Comp.2

Low suction / liquid

Check: refrigerant

Circuit

1 = Non critical

AL056 SCR Temp. Comp.2

Indicates insufficient cooling

to the SCR plate

Check: alarms

limits in the

compressor

1 = Non critical

AL057 System Lockout Comp.2

When a SCR / inverter / cavity

temperature fault occurs more

than 3 time in 30 minutes

Check: motor

cooling line and

solenoids valves /

cycle power

1 = Non critical

AL058 Inverter Temp. Comp.3

The temperature of the

compressor inverter is high

Check: liquid line

to the compressor

/ solenoid valves

1 = Non critical

AL059 Discharge Temp. Comp.3

The temperature of the

discharge gas is high

Check: refrigerant

charge / discharge

temperature

sensor

1 = Non critical

Alarms