Chillers turbochill™ air cooled and freecool – Airedale TurboChill FreeCool 200kW - 1830kW User Manual

Page 30

Advertising
background image

30

Introduction

Chiller Technical Manual 7525355 V1.1.0_04_2013

Chillers

TurboChill™ Air Cooled and FreeCool

Temperature Control

The microprocessor controller shall monitor the return and supply temperatures. The supply temperature is used to

calculate the required cooling demand. Further calculations are then made to determine the optimum compressors to be

selected and their individual cooling demands. These calculations ensure the unit efficiency is maximised under all load

conditions. As standard, the microprocessor controller can provide an infinite capacity control between 15% and 100%,

depending on the component selection. Refer to mechanical data tables for unit specific control ranges.

Monitoring

The microprocessor shall also monitor and display the following measured parameters:

Supply water temperature

Return water temperature

Liquid pressure

Suction pressure

Evaporator differential water pressure

Alarm Handling

The controller shall log and allow viewing of the last 150 conditions recorded in descending chronological order through

the keypad display.

The following conditions shall be detected, triggering a visual display:

High compressor discharge temperature (per compressor)

Low supply temperature

Phase rotation

Emergency stop

Evaporator flow failure

Low pressure safety switch

Low suction pressure (per compressor)

High liquid pressure

Compressor 1 contactor status

Compressor 2 contactor status (dependant on model)

Volt free contact non-critical alarm indication

Volt free contact critical alarm indication

Building Management Systems (BMS)

Sequencing (Master / Slave and Run / Standby) via the Airedale sequence manager.

Please specify at time of enquiry.

Chiller Sequence Manager

For the efficient temperature and capacity operation of multiple units on a single site, the sequence manager will permit

interlinked operation of the complete system thereby providing optimum temperature control and minimum power

consumption.
Up to 6 units can be sequenced.
Included within this package is a site visit by an Airedale Control Specialist to set up multiple unit sequence control.
The chiller sequence manager is supplied as a separate control panel to be mounted remotely in an indoor location,

such as a plant room.