Chillers turbochill™ air cooled and freecool, Te ch nic al, Air c oo led – Airedale TurboChill FreeCool 200kW - 1830kW User Manual

Page 49: Technical data

Advertising
background image

49

Chiller Technical Manual 7525355 V1.1.0_04_2013

Te

ch

nic

al

Chillers

TurboChill™ Air Cooled and FreeCool

A

ir C

oo

led

4

5

6

ELECTRICAL DATA

TCC11R06L-02

TCC11R08L-03

TCC11R10L-03

Unit Data
Full Load Amps

(1)

A

235.8

244.4

253

Maximum Start Amps

A

2

2

2

Mains Supply

VAC

400V (±10%) 3PH 50Hz

Recommended Mains Fuse Size

A

250

315

315

Max Mains Incoming Cable Size (Direct to 3 Phase Mains Isolator)

mm²

2x 300mm² (Torque >20Nm)

Independent Permanent Supply Recommended Fuse Size

A

25

25

25

Independent Permanent Supply

VAC

230V 1PH 50Hz (±10%)

Max Permanent Incoming Cable Size (Direct to Control Panel Isolator)

mm²

6mm² / 8 AWG

Control Circuit

VAC

24 VAC & 230VAC (±10%)

Evaporator
Immersion Heater Rating

W

500 (2x 250)

500 (2x 250)

500 (2x 250)

External Trace Heating
Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)
Quantity

6

8

10

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15

15

15

Motor Rating

kW

1.8

1.8

1.8

Condenser Fan - Per Fan (EC)
Quantity

6

8

10

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Condenser Fan - Per Fan (EC High Air Volume)
Quantity

6

8

10

Full Load Amps

A

4.8

4.8

4.8

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

3.10

3.10

3.10

Compressor - Per Compressor
Nominal Run Amps

A

210

210

210

Quantity

1

1

1

Motor Rating

kW

129

129

129

Start Amps

A

2

2

2

Type Of Start

Electronic Soft Start

Technical Data

Electrical

TCC11R06L-02, TCC11R08L-03, TCC11R10L-03

(1) Based at full load Conditions and AC Standard Fans

Pump electrical data is avaliable from Airedale upon request.

Advertising
This manual is related to the following products: