Chillers turbochill™ air cooled and freecool, Desi gn – Airedale TurboChill FreeCool 200kW - 1830kW User Manual

Page 37

Advertising
background image

37

Chiller Technical Manual 7525355 V1.1.0_03_2013

D

esi

gn

Chillers

TurboChill™ Air Cooled and FreeCool

Capacity Data

For guidance, a number of units from 200 kW to 900 kW at nominal conditions and at both fan speeds have been pre-

selected and used throughout this manual for information only.

Please contact Airedale with your specific requirements and we will be pleased to provide you with an individually

tailored selection and technical detail.

Operating Limits

(For 100% Water) Standard Unit

Minimum ambient air DB

-20°C

Maximum ambient air DB at full load operation

35°C

Maximum ambient air DB at reduced load operation

40°C

Minimum supply water temperature

+5°C

Maximum return water temperature

+26°C*

Maximum supply water temperature

18°C

Minimum / maximum ΔT

4K / 8K

* With an 8K ∆T