Chillers turbochill™ air cooled and freecool – Airedale TurboChill FreeCool 200kW - 1830kW User Manual

Page 40

Advertising
background image

40

Chiller Technical Manual 7525355 V1.1.0_03_2013

D

esi

gn

Chillers

TurboChill™ Air Cooled and FreeCool

Sound Data

Measurement of Sound Data

All sound data quoted has been measured in the third-octave band limited values, using a Real Time Analyser calibrated

sound intensity meter in accordance with BS EN ISO9614 Part 1:1995. The Global sound data quoted is valid for noise

emitted in the horizontal plane in all directions.

All Sound Power Levels quoted are calculated from measured sound intensity according to BS EN ISO9614 Part 1:

1995.

Sound Pressure Levels are calculated from sound power using the expanded parallelepiped method according to BS

EN ISO 11203: 1996.

Sound Directivity

The Global sound measurements quoted in the following tables do not incorporate any directivity or denote any sound

level heard at any given position surrounding the unit, rather they represent the total sound level radiating from the unit

in all directions in the horizontal plane from source.

Using the adjustment factors from the map below, partial sound power levels can be derived from the global sound

power data.

-4

-4

-11

-9

EXAMPLE (dB(A)):

470 kW

Output - Quiet Models - TCC12R08S-04
Overall Sound Power of 89 dB(A) =

Base Correction Values -

Global dB

80 dB(A)

85 dB(A)

78 dB(A)

85 dB(A)