Turbocor compressor, Chillers turbochill™ air cooled and freecool, Introduction – Airedale TurboChill FreeCool 200kW - 1830kW User Manual

Page 18

Advertising
background image

18

Introduction

Chiller Technical Manual 7525355 V1.1.0_04_2013

Chillers

TurboChill™ Air Cooled and FreeCool

Turbocor Compressor

Turbocor centrifugal compressor supplied with as standard:

Suction and discharge shut off valves

Discharge non-return valve

Line reactor (for removing additional impedance harmonics and voltage

spikes in the ac waveform)

EMI/EMC filter and comprising of:

o

AC-DC rectifier

o

DC capacitors

o

DC-AC (IGBT) converter

o

Motor/bearing management system and incorporated surge

protection

o

Soft start module

o

Magnetic bearing system

o

The compressors are mounted on Turbocor specially designed

vibration reducing isolating rubber mounts

o

Linear capacity modulation is provided by a variable frequency

drive

Key benefits of Turbocor compressor technology:

Oil Free Operation

More efficient use of heat exchangers

No oil entrainment issues – pipe work can be optimised for

performance not oil return

Variable speed operation offering exact capacity match and optimum

part load performance

Magnetic bearing system constantly optimises shaft / impeller

position

Small and light, only 120kg or 132kg (compressor size dependant)

No mechanical contact, very quiet operation

Very low start current, only 2A

The intelligent, self optimising compressor offers near silent, oil free

operation and ultra efficient variable speed control

Turbocor compressor shaft and impellers levitate on a magnetic

cushion eliminating friction and vibration resulting in the compressor

running at a smooth and reduced sound spectrum

The TurboChill compressor’s variable speed control offers 2 major

benefits:

o

Uses substantially less power at part load and gives accurate

set-point control and exact capacity match

o

The inbuilt electronic soft start produces a very low starting

current of just 2A and eradicates the need to oversize

electrical supply components on site