Chillers turbochill™ air cooled and freecool, Te ch nic al, Fre ec oo l – Airedale TurboChill FreeCool 200kW - 1830kW User Manual

Page 93: Sound data - tcf tcf - ac fans

Advertising
background image

93

Chiller Technical Manual 7525355 V1.1.0_04_2013

Te

ch

nic

al

Chillers

TurboChill™ Air Cooled and FreeCool

Fre

eC

oo

l

Sound Data - TCF

TCF - AC Fans

AC

Single Octave Sound Levels (dB)

63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall

[dB(A)]

TCF11X06S-07

Power

82

83

82

77

77

73

77

81

85

Pressure @ 10m

50

51

49

45

45

41

45

49

52

TCF11X08S-07

Power

83

84

83

78

77

74

77

81

85

Pressure @ 10m

51

52

50

45

45

41

45

49

52

TCF11X06L-11

Power

82

83

81

79

82

75

76

80

86

Pressure @ 10m

50

51

49

46

49

43

44

47

53

TCF11X08L-08

Power

83

84

82

79

82

75

76

80

86

Pressure @ 10m

51

52

50

47

49

43

43

47

53

TCF11X10L-10

Power

84

85

83

80

82

76

76

80

86

Pressure @ 10m

51

52

50

47

49

43

43

47

53

TCF12X08S-09

Power

83

84

83

79

80

76

80

84

87

Pressure @ 10m

51

52

50

47

47

43

48

52

55

TCF12X10S-05

Power

84

85

84

80

80

76

80

84

88

Pressure @ 10m

51

52

51

47

47

43

47

51

55

TCF12X12S-05

Power

85

86

85

80

80

76

80

84

88

Pressure @ 10m

52

53

51

47

47

43

47

51

55

TCF12X14S-05

Power

86

87

85

81

80

76

80

84

88

Pressure @ 10m

52

53

52

47

47

43

47

51

55

TCF12X12L-12

Power

85

86

84

82

85

78

79

83

89

Pressure @ 10m

52

53

51

49

52

45

46

50

56

TCF12X14L-12

Power

86

87

85

82

85

78

79

83

89

Pressure @ 10m

52

53

51

49

51

45

46

49

55

TCF12X16L-12

Power

86

87

85

82

85

78

79

83

89

Pressure @ 10m

53

54

52

49

51

45

45

49

55

TCF12X18L-13

Power

87

88

86

82

85

79

79

83

89

Pressure @ 10m

53

54

52

49

51

45

45

49

55

TCF12X20L-13

Power

87

88

86

83

85

79

79

83

89

Pressure @ 10m

53

54

52

49

51

45

45

49

55

(1) dB(A) is the overall sound level, measured on the A scale.