Performance Effects of Glycol

Glycol Data

For a given percentage of glycol in the system there are correction factors that need to be applied, the following tables

can be used as a guide.

CAUTION

The source data must be 100% water for the correction factors to be valid.

Ethylene Glycol Nominal Correction Factors

Glycol in System / Freezing Point °C

10% / -4°C

20% / -9°C

30% / -15°C

40% / -23°C

Output (kW)

x

0.98

0.97

0.95

0.93

Compressor Input (kW)

0.99

0.98

0.96

0.95

Water Flow (l/s)

0.99

1.02

1.04

1.07

Pressure Drop (kPa)

1.05

1.20

1.38

1.57

Propylene Glycol Nominal Correction Factors

Glycol in System / Freezing Point °C

10% / -2°C

20% / -6°C

30% / -12°C

40% / -20°C

Output (kW)

x

0.97

0.95

0.91

0.88

Compressor Input (kW)

0.99

0.98

0.96

0.95

Water Flow (l/s)

0.98

0.97

0.95

0.95

Pressure Drop (kPa)

1.08

1.17

1.31

1.45

Example:

At 100% Water:

Output

=750

kW

Compressor Input

=228.6 kW

Flow Rate

=35.83 l/s

Pressure Drop

=20.6 kPa

Ambient

=35°C

Inlet Fluid Temp.

=7°C

Outlet Fluid Temp.

=12°C (5K ∆T)

To 20% Ethylene Glycol:

100% Water

Multiplier

20% Ethylene Glycol

Output (kW)

750

x 0.97

727.5 kW

Compressor Input (kW)

228.6

x 0.98

224.0 kW

Water Flow (l/s)

35.83

x 1.02

36.55 l/s

Pressure Drop (kPa)

20.6

x 1.20

24.72 kPa