System, System 131, Chillers turbochill™ air cooled and freecool – Airedale TurboChill FreeCool 200kW - 1830kW User Manual

Page 131

Advertising
background image

131

Chiller Technical Manual 7525355 V1.0.0_04_2013

M

ain

te

nanc

e

Chillers

TurboChill™ Air Cooled and FreeCool

Unit Operation Checks

Record the following operating conditions of the unit at stable conditions:

Suction pressure (bar)

Liquid pressure (Bar)

Discharge pressure (Bar)

Suction temperature (°C)

Liquid temperature (°C)

Discharge temperature (°C)

Superheat (°C)

Sub cooling (°C)

Water return temperature (°C)

Water supply temperature (°C)

Low supply water trip

To check operation of the low temperature trip the following procedure can be carried out.

With the unit running increase the low temperature limit to the actual supply water temperature.

This will trip the unit in a safe manner without risk of freezing the evaporator.

Return the low temperature limit to correct value after test (this will allow the unit to operate correctly).

Liquid line sight glass

Record the status of the liquid line sight glass:

Clear / Flashing

Wet / Dry

The sight glass is used to indicate:

The condition of the refrigerant in the system

Lack of refrigerant

Moisture content of the refrigerant

The colour of the sight glass depends on the moisture content of the refrigerant. The recommended moisture levels of a

system should be below 75ppm.
An indication of green / dry are to be considered as perfect conditions meaning full protection by the filter drier against

effects from moisture.
If the green colour starts to fade, the colour change from green to yellow has begun and the indicator should therefore

be watched carefully. If the colour changes to yellow it is a clear signal that the capacity of the filter drier is exceeded

and should be replaced as soon as possible.

F-Gas Leak Detection Checks

Perform an F-Gas refrigerant leak detection on the unit and ensure no refrigerant leaks are found.

Maintenance

System

Task

Frequency

System

3 Mths

12 Mths

60 Mths

Check the following against the commissioning records:

Record operating conditions.

Water on / off temperatures.

Water pressure drop.