BMS Interface Card

BMS system configuration by others.

Enables units to be interfaced with most BMS, factory fitted, please contact Airedale.

A wide range of protocols shall be accommodated through the use of interface devices. Available as a standard option

are: ModBus / Jbus, Carel, Trend, SNMP, LonWorks, Metasys and BACnet

Also available shall be Airedale’s own supervisory plug-in BMS card pCOWEB.

Based on Ethernet TCP/IP secure technology with SNMP features.

Requires no proprietary cabling or monitoring software and supplied pre-programmed with an IP address for ease of

setup.

Modbus / Carel BMS Connection

The Airedale controllers shall be able to communicate directly using the Modbus® protocol.

The Modbus® card shall be a small PCB (60mm x 30mm), which is plugged into the controller to provide it with the

following protocol support

Modbus® - JBus slave

RTU mode (Remote Terminal Unit) with 8 bit encoding and error handling using 16 bit CRC

Communication standard connection options of RS485 (multipoint) or RS232 (point-point)

Maximum Baud Rate of 19200

The data communication shall be asynchronous serial, 8 data bits, 2 stop bits and no parity (in total 11 bits/datum).

The data/parameters from the controller shall be represented within Modbus® registers, each register containing

information pertaining to temperatures, pressures, setpoint and status etc. shall be available to the site integration

company in a spreadsheet format

Lon BMS Connection

The Airedale controllers, using special serial cards, shall be integrated into LonWorks® networks. The RS485 and the

FTT10 standards shall be supported by the LonWorks® serial cards.

The two types of LonWorks® serial cards shall differ by the type of interface on the LonWorks® network side:-

FTT-10A 78 kbs (TP/FT-10)
RS485 39 kbs (TP/485-39)

pCOWeb

pCOWeb is a new generation of Airedale supervisory plug-in cards which make communicating with an Airedale unit

simply a matter of logging onto the office Intranet or via the web.

Based on Ethernet TCP/IP secure technology, pCOWeb shall require no proprietary cabling. It shall have little or no

setup on site and can be pre-programmed with an IP address prior to dispatch from airedale.

CAUTION

When adding to an existing controls scheme, please consult Airedale Controls to ensure strategy compatibility.

Advertising
This manual is related to the following products: