Interconnecting wiring, Chillers turbochill™ air cooled and freecool, Interconnecting wiring general – Airedale TurboChill FreeCool 200kW - 1830kW User Manual

Page 117

Advertising
background image

117

Chiller Technical Manual 7525355 V1.1.0_04_2013

In

sta

lla

tio

n

Chillers

TurboChill™ Air Cooled and FreeCool

TURBOCHILL

L1

Mains Incoming Supply 400V/3PH/50Hz
(Direct to 3 Phase Isolator)

L2

L3

E

L4

Separate Permanent Supply 230V/1PH/50Hz

N

E

L4

External Trace Heating Connections

N

240V/500W max

502

(1) Remote Pump Interlock 24VAC

508

502

(1) Evaporator Pump Water Flow Switch 24VAC

506

502

Unit Remote On/Off 24VAC

507

Setback Setpoint Temperature Switch

502

510

581

Non-

Critical

Alarm

Volt Free Common Alarm

580

Volt Free Alarm N/O

582

Volt Free Alarm N/C

591

Critical

Alarm

Volt Free Common Alarm

590

Volt Free Alarm N/O

592

Volt Free Alarm N/C

RX-/Tx-

Network Connections (Inward Connection)

RX+/Tx+

GND

RX-/Tx-

Network Connections (Outward Connection)

RX+/Tx+

GND

(Direct to Control Panel Isolator)

Interconnecting Wiring

General

As standard the equipment is designed for 400V, 3 phase, 3 wire 50Hz and a separate permanent 230V, 1 phase, 50Hz

supply, to all relevant IEE regulations, British standards and IEC requirements.
The control voltage to the interlocks is 24V, always size the low voltage interlock and protection cabling for a maximum

voltage drop of 2V.
Avoid large voltage drops on cable runs, particularly low voltage wiring.

CAUTION

A fused and isolated electrical supply of the appropriate phase, frequency and voltage should be installed.

Wires should be capable of carrying the maximum load current under non-fault conditions at the stipulated voltage.

A separately fused permanent single phase and neutral supply MUST BE FITTED for the evaporator trace heating and

control circuits,

FAILURE to do so will INVALIDATE WARRANTY.

CAUTION

ALL work MUST be carried out by technically trained competent personnel.

Isolate REMOTELY the mains incoming supply to the BUSBAR chamber prior to maintenance or repair work.

CAUTION

(1) MUST be directly wired to the chiller to validate warranty.