Liquid level sensor, Chillers turbochill™ air cooled and freecool, Te ch nic al – Airedale TurboChill FreeCool 200kW - 1830kW User Manual

Page 119: Fre ec oo l

Advertising
background image

119

Chiller Technical Manual 7525355 V1.1.0_04_2013

Te

ch

nic

al

Chillers

TurboChill™ Air Cooled and FreeCool

Fre

eC

oo

l

Liquid Level Sensor

The liquid level sensor is designed to measure the amount of refrigerant inside the flooded evaporator of a Turbochill

and send a current signal between 4 and 20mA to the microprocessor.
This signal is used by the controller to control the flow of refrigerant into the evaporator for optimal and energy efficient

performance. The liquid level sensor will be calibrated and located on the evaporator upon dispatch of the unit. However

in the following section there is a quick guide on how to reset and recalibrate the sensor.

Ok key

Move to the menu overview

Confirm selected menu

Edit parameter

Save Values

key to select

Menu Change

List entry

Select editing position

+ key

Change value of the parameter

ESC key

Interrupt input

Jump to the next higher menu

Setup instructions / guide The liquid level sensor is used to monitor the level of refrigerant inside the evaporator by sending a 4 to

20mA signal to the controller. The transmitter then governs the amount of refrigerant in the evaporator.

Step 1 Apply power

To set-up the sensor, power needs to be applied. This can be done by turning on the breaker within the control

panel. After power is applied the level sensor does an internal check for 30 seconds. This check includes the

internal electronics, the sensor type etc. The output signal jumps briefly to the fault condition (10 seconds.)

Step 2
Minimum adjustment

Through the menu structure “Basic adjustment”, select the “min adjustment”. Set to 0.00% (58.00 pF)

Step 3
Maximum adjustment

Set the maximum adjustment Set to 100.00% (101.00 pF)

Step 4
Damping

Set the damping to “0”. This suppresses any fluctuation in the display level.

Further information

Further information is available from Airedale upon request.

LOC

K

TWIST

OP

EN

+

OK

ESC

1

2

3

1.1