Chiller Technical Manual 7525355 V1.0.0_04_2013

M

ain

te

nanc

e

Chillers

TurboChill™ Air Cooled and FreeCool

Maintenance

Refrigeration

Service Tools / Test Equipment

Refrigerant Manifold Gauges

Spanners

Voltmeter

Safety Equipment

Safety Glasses / Goggles

Gloves

Overalls

Procedures

HP / LP Safety Pressure Switch Settings

Check operation of HP/LP cut-out.

Settings

LP cut-out – (Auto reset for 3 times when the Low Pressure is detected over a period of 1 hour)
Has a 2 minute delay on start-up (similar to a Low ambient kit)
Low pressure cut-out 0.29 +/- 0.2 Barg
HP switch (Manual reset): High pressure switch 17.5 Barg +/- 0.7 Barg
HP limiting function 15.0 Barg / 1.5 Barg differential

Task

Frequency

3 Mths

12 Mths

60 Mths

Refrigeration

Compare the following and compare results

with commissioning records:
Suction, liquid and discharge pressures.

Refrigeration system temperatures, suction, liquid and

discharge. Record superheat and sub cooling temperatures.

Check each circuit sight glass for dryness

and bubbles for indication of leaks.

Head pressure control is maintained.

Record details on F-Gas record.

Pressure relief valves. (replace in

accordance to building insurance)